Description
CVM-C4-ITF-485-ICT2, Power analizer, panel mounted 96×96
Code: M52706.
- Protocol: Modbus/RTU
- Communications: RS-485
- Transistor output: 2
- Nº relays: 2
- Digital inputs: 2
- Measuring current Channels: 3
- Input current: …/5 A | …/1 A
- Mounting: Pannel
INFORMATION
DESCRIPTION
CVM-C4 is a power analyser that measures, calculates and displays the main electrical parameters for single-phase and three-phase networks (with or without neutral) on its screen. Measurement is made in true rms value, by means of 3 AC voltage inputs and 3 /5 A or /1 A current inputs. Relay outputs enable local operation in the event of an alarm event being triggered. Its dimensions are 96 x 96 mm with a depth of only 41.5 mm. Current measurement is indirectly carried out by /5A or /1A transformers. It allows AC (80…270 Vac)and DC (80…270 Vdc or 18… 36 Vdc power supply systems). It features RS-485 communications enabling remote data readout or Scada or Master centralisation.
APPLICATIONS
- For electrical parameter measurement in areas whose reduced dimensions require the installation of a space-saving panel analyser.
- Instantaneous value measurement of electrical parameters with communications.
- Logging of consumed or generated Active or Reactive Energy.
- The device’s relay outputs allow the installation to be locally operated.
- Programmable alarms by setting relay activation time, connection delay and hysteresis.
- 5000 imp/kWh energy impulse outputs
- Energy measurement of two different sources on 2 separate meters (by digital input activation).
- Voltage and current THD% measurement to check for harmonics in the installation.
- SPECIFICATIONS
- AC POWER SUPPLY
- Installation category
- CAT III 300V
- Consumption
- 6 … 18 VA
- Frequency
- 50/60 Hz
- Nominal voltage
- 80 … 270 Vac
- DC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 5 … 1.8 W
- Nominal voltage
- 80…270 Vdc
- MECHANICAL CHARACTERISTICS
- Size (mm) width x height x depth
- 96 x 96 x 41.5 (mm)
- Envelope
- Polycarbonate + ABS
- Torque setting
- 5 Nm
- Communications cable cross-section
- 5 mm2
- Cable gauge at power supply terminals
- 5 mm2
- Cable gauge at input and output terminals
- 2,5 mm 2
- Cable gauge at current terminals
- 2,5 mm2
- Cable gauge at voltage terminals
- 5 mm2
- Weight (kg)
- 0,268
- ENVIRONMENTAL CHARACTERISTICS
- Protection class
- Front: IP54, Rear: IP20
- Relative humidity (without condensation)
- 5 … 95%
- Storage temperature
- -20 … +70 ºC
- Working temperature
- -10 … +60 ºC
- CURRENT MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Consumption
- < 0.2 VA (por fase)
- Nominal current (In)
- 1 A / 5 A ~
- Allowable overload
- 2 In continuous, 10 In instantaneous(5s)
- VOLTAGE MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Consumption
- < 0.2 VA (por fase)
- Sampling frequency
- 45…65 Hz
- Input impedance
- > 1.7 MΩ
- Nominal voltage
- 100…277 V~ Ph-N (± 8%)
- Maximum permanent measurement voltage
- 2 Un continous, 2 Un instantaneous
- COMMUNICATIONS
- Data bits
- 8
- Stop bits (ModBus)
- 1-2
- Parity
- non-pair-impar
- Protocol
- ModBus RTU
- Speed
- 2400-4800-9600-19200
- STANDARDS
- Electrical safety, Maximum height (m)
- 2000
- Electrical safety, Installation category
- CAT III 300 V
- Electrical safety, Contamination level/class
- Pollution resistance 2
- Standards
- IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
- USER INTERFACE
- Keyboard
- 3 keys
- Display type
- LCD
- DIGITAL INPUTS
- Input/output insulation
- 3,75 kV RMS
- Quantity
- 2
- Type
- Potential-free contact
- Maximum short-circuit current
- 4 mA
- Maximum open circuit voltage
- 30 V
- DIGITAL RELAY OUTPUTS
- Quantity
- 2
- Type
- Relay
- Resistive load (max.)
- 250 Vca / 5 Aca, 30 Vcc / 5 Acc
- Maximum current
- 5 A ~
- Maximum open contact voltage
- 277 V ~ / 30 Vdc
- Electrical life
- (250 V ~ / 5 A) 1 x 105
- Maximum switching capacity
- 1385 VA / 150 W
- DIGITAL TRANSISTOR OUTPUTS
- Pulse width
- Minimum pulse width: 80mA
- Type
- Passive impulse
- Maximum frequency
- 10 Hz
- Maximum current
- 27 mA
- Maximum voltage
- 27 Vcc
- MEASUREMENT ACCURACY
- Frequency measurement
- 5 %
- Phase current measurement
- 2 %
- Reactive energy measurement (kvarh)
- 5 %
- Reactive power measurement (kvar)
- 5 %
- Active energy measurement (kWh)
- 5 %
- Active power measurement (kW)
- 5 %
- Phase voltage measurement
- 2 %
Reviews