Description
CVM-C10-mV-485-ICT2, Power analyzer
Code: M559210000V00
- Protocol: Modbus/RTU | BACnet
- Communications: RS-485
- Transistor output: 2
- Nº relays: 2
- Digital inputs: 2
- Measuring current Channels: 3
- Harmonics: 31
- Input current: …/333 mV
- Mounting: Pannel
- Modules: 96 x 96
INFORMATION
DESCRIPTION
The CVM-C10 is a panel mounted (96 x 96 mm) power analyzer that records energy values. Compact and versatile, with 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits,
two-phase circuits with or without neutral, single-phase circuits or ARON connections.
Display features and interface:
- Backlit touch-screen (capacitive)
- Analogue display of instantaneous parameters (power, maximum power reached and cos φ or PF)
- Backlit display
- Alarm LED indicator.
- Tariff cost
- Operating hour indicator for preventive maintenance
APPLICATIONS
- Record the energy consumption from three different sources: network, generator set or photovoltaic energy generation system.
- Generation of an impulse signal associated with the cost, kgCO2 emissions or savings, according to the consumption or generation of energy.
- Selection of tariffs with digital inputs. Perfect to calculate costs in three different work shifts.
- Programs alarms on any instantaneous parameter measured or calculated. Configurable parameters: Low/High, hysteresis (%), NO/NC,
connection/disconnection delay and interlocking.
- SPECIFICATIONS
- AC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 4 … 6 VA
- Frequency
- 50 … 60 Hz
- Nominal voltage
- 95 … 240 V ~ ± 10%
- DC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 2 … 6 W
- Nominal voltage
- 105 … 272 Vdc ± 10%
- MECHANICAL CHARACTERISTICS
- Size (mm) width x height x depth
- 96 x 96 x 60.9 (mm)
- Envelope
- Self-extinguishing V0 plastic
- Fastening
- Panel
- Weight (kg)
- 0,3
- ENVIRONMENTAL CHARACTERISTICS
- Protection class
- IP 51 (Front), IP 64 (with accessory), IP 21 (rear)
- Relative humidity (without condensation)
- 5 … 95%
- Storage temperature
- -10… +50 ºC
- Working temperature
- -5 … +45 ºC
- STANDARDS
- Certifications
- UL/CSA 61010-1 3rd edition, UL, VDE
- Electrical safety, Maximum height (m)
- 2000
- Standards
- UNE EN 61010, UNE EN 61000-6-3, UNE EN 61000-6-1, IEC 664, VDE 0110, UL 94, BS EN 61000-6-2, BS EN 61000-6-4
- CURRENT MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Nominal current (In)
- 333 mV
- Phase current measuring range
- 2 … 120% In
- Maximum input current consumption
- 0,033 mVA
- Maximum pulse current
- 1,2 In
- Minimum current measurement
- 66mV
- VOLTAGE MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Input impedance
- 440 kΩ
- Frequency measuring range
- 45 … 65 Hz
- Voltage measuring range
- 5 …120% Un
- Nominal voltage
- 300V Ph-N, 520V Ph-Ph
- Minimum measurement voltage (Vstart)
- 15 V
- COMMUNICATIONS
- Fieldbus (BACnet)
- MS/TP
- Fieldbus (ModBus)
- RS-485 / RTU
- Stop bits (BACnet)
- 1
- Stop bits (ModBus)
- 1-2
- Parity (BACnet)
- non
- Parity
- non-pair-impar
- Protocol
- ModBus/BACnet
- Speed
- 9600-19200
- USER INTERFACE
- LED
- 3 LED
- Keyboard
- Capacitive, 3 keys
- Display type
- LCD Custom COG
- DIGITAL INPUTS
- Input/output insulation
- Optoisolated
- Quantity
- 2
- Type
- NPN Potential-free contact
- DIGITAL RELAY OUTPUTS
- Electrical life (at maximum load)
- 60×103cycles
- Mechanical life
- 10×106cycles
- Maximum switching capacity
- 1500 VA
- DIGITAL TRANSISTOR OUTPUTS
- Pulse width
- 30 ms a 500 ms (Programmable)
- Quantity
- 2
- Type
- NPN salida
- Maximum frequency
- 16 imp / s
- Maximum current
- 50 mA
- Maximum voltage
- 24 Vdc
- MEASUREMENT ACCURACY
- Phase voltage measurement
- 5% ± 1 digit
Reviews