Description
10-QD1B-90B10, Three-phase energy meter direct connection
Code: QB4H0
- Communications: RS-232 | RS-485
- Class (Active/Reactive): B (1) / 2
- System: Three-phase
- Measure: Direct
- Measurement Range (V): 3×230/400
- Measurement Range (A): 10 (100)
- Quadrants: 4
- Frequency (Hz): 50
INFORMATION
DESCRIPTION
CIRWATT-B410D is a standard three phase direct connection meter, ideal for industrial three-phase applications. With class B in active energy according to European Directive MID (EN 50470) or class 1 according to IEC-62053-21, it has multiple communication options and expansion modules that allow it to adapt to any type of installation.
APPLICATIONS
CIRWATT-B410D is suitable device for LV applications (for currents up to 100 or 120 A maximum), adapting to new market needs with great versatility in its communication options and expansion modules. Available in 2 quadrants for energy consumption or 4 quadrants for photovoltaic plants (generation and consumption of energy).
SPECIFICATIONS
AC POWER SUPPLY
Tolerance
80 % … 115 % Un
Consumption
< 2 W; < 10 VA
Frequency
50 / 60 Hz
Nominal voltage
3 x 230 (400) V – 3 x 127 (230) V
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth
172 x 255 x 67 (mm)
Envelope
DIN 43859
ENVIRONMENTAL CHARACTERISTICS
Relative humidity (without condensation)
95 % max.
Storage temperature
-40 … +85 ºC
Working temperature
-40 … +70 ºC
VOLTAGE MEASUREMENT CIRCUIT
Connection
Asymmetrical
Consumption
< 2 W; 10 VA
Nominal frequency
50 / 60 Hz
Nominal voltage
3 x 230/400 V (Request for other configurations)
CURRENT MEASUREMENT CIRCUIT
Consumption
< 0,1 V·A
Reference current (Iref)
10 A
Maximum current
100 A
Minimum current measurement
< 0,5 x Itr
COMMUNICATIONS
Protocol
REE, basado en IEC 870-5-102
Type
RS-232 / RS-485
OPTICAL COMMUNICATION INTERFACE
Hardware
IEC 62056-21
Protocol
REE, based on IEC 870-5-114
Type
Serial;bi-directional
USER INTERFACE
Resolution of the display
up to 8 digits (8 mm)
Display type
LCD
MEMORY
Format
Serial flash
Internal memory
Data: non-volatile memory, Setup and events: serial-flash
Write time
4000
INTERNAL BATTERY
Type
Lithium
Useful life
> 20 years @ 30 ºC
PLC
Hardware
CENELEC A or CENELEC B
Protocol
CirPLC & PEP (PLC Encapsulated Protocol)
Modulation system
DSCK with repeater system
MEASUREMENT ACCURACY
Reactive energy measurement (kvarh)
IEC 62053-23 (Class 2)
Active energy measurement (kWh)
EN 50470 (Class B) IEC 62053-21 (Class 1)
FEATURES / PERFORMANCE
Billing closures
12 locks per contract. Programable date and hour
Load curve
2 load curves, programmable integration time (1 … 253 min)
Optional
Communications: RS-232 / PLC ,RS-485 / PLC, RS-232 / RS-232 , RS-485 / RS-485, RS-232 / RS-485, RS-232 / Ethernet, R-485 / Ethernet. Expansion boards: No inputs / outputs, 4 relay outputs (Rate Indicator), 2 relay inputs / 4 pulse outputs, 4 pulse inputs, Differential current measurement, 2 relay outputs / 2 pulse outputs, / 2 pulse inputs
Tariff programming
12 days 10 types of data 9 types of tariffs 30 public holidays 12 special days
CLOCK
Source
Temperature compensated oscillator
Accuracy (EN 61038)
< 0,5 s/day (23 ºC)
Type
Gregorian calendar