Description
CLZ-FP-44/15-HD, Three-phase tubular power capacitor
Code: R2H54E.
- Terminal: A
- Frequency (Hz): 50
- kvar (400 V): 12,5
- kvar (440 V): 15
- Cover (opc.): 1
- Use voltage (V): 400 | 440
INFORMATION
DESCRIPTION
CLZ-HD (Heavy duty) capacitor range is composed of capacitors with a tubular casing, of the dry-type, covering a wide range of power and voltage ratings, at 50 and 60 Hz. The CLZ-HD capacitors are designed to be installed in installations with extreme working conditions. The design, manufacturing and testing processes guarantee the production of top quality and long lasting capacitors. Those CLZ capacitors offer a new refrigeration technology by means of nitrogen gas*, being a refrigerating system of high benefits, inert and non flammable.
APPLICATIONS
Its application is based on compensation in installations with static or variable loads (capacitor banks). Especially designed to be installed in roughly environments with the most extreme conditions due to its longer life and high temperature resistance.
SPECIFICATIONS
AC POWER SUPPLY
Frequency
50 Hz
ELECTRICAL CHARACTERISTICS
Losses (W)
Dielectric: < 0,2 W / kvar Total: < 0,4 W / kvar
Discharge resistance
50 V / 1 min (0,5 – 30 kvar) 75 V / 3 min (33 – 50 kvar)
Surge
10 % 8h in 24 h 15 % up to 30 min in 24 hours 20 % up to 5 min in 24 hours 30 % up to 1 min in 24 hours
Tolerance C
-5 … +10 %
Maximum phase current
400 x In
Voltage
440 V
Insulation voltage, circuit
3 / 8 kV
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth
85 x 276 x 85 (mm)
Envelope
Aluminum
Torque setting
1,2 … 1,7 Nm / Earth: 5 Nm máx.
Cable gauge at input and output terminals
16mm2
Fastening
M12 fastening screws earth conductor
Ventilation
Natural or forced depending on the cabinet
Weight (kg)
1,09
ENVIRONMENTAL CHARACTERISTICS
Protection class
IP 20 / IP 54 with terminal cover (optional) (for models Ø 85, 100, 116 mm)
Relative humidity (without condensation)
95%
Installation, location, position.
Vertical / Horizontal. Minimum distance between condensers 2 cm.
Working temperature
Tª class D: Daily average: 45 ºC, annual average: 35 ºC, maximum: 65 ºC, minimum: -50 ºC
STANDARDS
Certifications
VDE 560
Electrical safety, Maximum height (m)
4000
Standards
IEC 60831-1-1/2
CURRENT MEASUREMENT CIRCUIT
Permanent overload
1,8 In
PROTECTION
Circuit breaker type
Dielectric regeneration Expansion system
Reviews
There are no reviews yet.