CVM-B100-ITF-485-ICT2

Compare
Category:

Description

CVM-B100-ITF-485-ICT2, Power analyzer

Code: M56011.

  • Protocol: Modbus/RTU | BACnet
  • Energy accuracy: 0,5 S (…/5A)
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Input current: …/5 A | …/1 A | …/250 mA
  • Mounting: Pannel
  • Modules: 96 x 96

 

INFORMATION

DESCRIPTION

The CVM-B100 and CVM-B150 units are panel mounted three-phase power analyzers (dimensions: 96×96 and 144×144 mm, respectively). Both offer 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.

The CVM-B100 and CVM-B150 high-performance units feature a measurement engine that allows the user to analyse many different electrical parameters, in addition to offering a large variety of optional expansion modules for the same unit.

Features:

  • Format: 96×96 (CVM B100) and 144×144 (CVM B150)
  • High-resolution VGA colour screen
  • IP 65 front panel protection (with sealing joint)
  • 5 voltage inputs (3 phases + neutral + earth) 1000 Vf-f
  • 4 Current inputs, ITF
  • Class 0.2 voltage and current accuracy
  • Class 0.5S energy accuracy
  • Expandable unit, up to 4 modules, combining digital and analogue outputs, Modbus/TCP, MBus, LonWorks, Profibus, XML/Web
  • Modular (optional addition of expansion modules)
  • Touch-sensitive movement buttons
  • Universal power supply source
  • RS485 communications port (Modbus/RTU and BACnet protocols)
  • Customisation of parameters to be displayed
  • Operating hour indicator for preventive maintenance.

Other features:

  • Innovative SCV interface (Slide, Choose & View) for versatile data display, enabling the customisation of the parameters displayed on the screen
  • Electrical parameters: instantaneous, maximum, minimum (with date and time) and demand
  • Incremental electrical parameters (energy), times, costs, emissions
  • 3 Tariffs (can be selected via the digital input or RS485 communications)
  • Capable of showing costs and kgCO2 emission sources on the screen, depending on the energy consumed or generated
  • 2 Relay outputs for alarms with delay, times, ON and OFF, etc.
  • 2 transistor outputs for alarms or impulse generation, with all the possible configuration parameters
  • 2 digital inputs, with control over the selection of the unit’s tariffs or configurable for monitoring purposes, with RS-485 Modbus communications, monitoring of logical states of other electromechanical units. (RCCBs, thermal-magnetic circuit breakers, etc.)

APPLICATIONS

  • Control and monitoring of all electrical parameters measured in any electric distribution panel and low and high-voltage connection points.
  • 4 alarms (2 per transistor and 2 per relay), fully and independently programmable: low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
  • Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours)
  • Transducer that converts analogue signals to any instantaneous parameter that the unit can measure or calculate, with built-in expansion modules with analogue outputs.
  • Display of process signals, with a built-in expansion module with analogue inputs; optional reporting of these signals to SCADA systems through communication systems
  • Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
  • Autonomous datalogger with web server, connected to a M-CVMAB-Datalogger module. Enables direct monitoring of the historical data stored in the unit via a conventional web browser.

400 Hz Applications

CVM-B150 provides a version adapted to 400 Hz networks specially designed for applications such as:

  • Aeronautical
  • Astronautics
  • Naval
  • Military
  • SPECIFICATIONS
  • AC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • máx. 23.9 VA
  • Frequency
  • 45 … 65Hz
  • Nominal voltage
  • 100 … 240 V ~
  • DC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 12.2 W
  • Nominal voltage
  • 120 … 300 Vdc
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 97 x 99 x 99 (mm)
  • Envelope
  • Self-extinguishing V0 plastic
  • Fastening
  • Panel 92×92
  • Weight (kg)
  • 0,516
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted)
  • Relative humidity (without condensation)
  • 5 … 95%
  • Storage temperature
  • -20… +80 ºC
  • Working temperature
  • -10…+60 ºC
  • STANDARDS
  • Certifications
  • UL 61010-1 3rd edition, CAN/CSA-C22.2 No.61010-1 3rd. edition 2012-05
  • Electrical safety, Maximum height (m)
  • 2000
  • Standards
  • IEC 61010-1 (1rd. Edition), UNE-EN 61000-6-2, UNE-EN 61000-6-4, IEC 60664-1, IEC 61010-2-030 (First Edition). Measurement according to IEC 61557-12
  • CURRENT MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 600 V
  • Nominal current (In)
  • …/5A, …/1A, …/0.250A
  • Phase current measuring range
  • 01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A)
  • Neutral current measuring range
  • 02…0.5A (…/0.250A, calculated)
  • Maximum input current consumption
  • 0,9 VA
  • Maximum pulse current
  • 100 A
  • Minimum current measurement
  • 0,01 A (…/5A, …/1A, …/0,250A
  • VOLTAGE MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 600V
  • Input impedance
  • 2MΩ
  • Frequency measuring range
  • 40…70Hz
  • Voltage measuring range
  • 20…600 V~
  • Maximum input voltage consumption
  • 0,15VA
  • Minimum measurement voltage (Vstart)
  • 10 V~
  • COMMUNICATIONS
  • Fieldbus (BACnet)
  • MS/TP
  • Fieldbus (ModBus)
  • RS-485 / RTU
  • Stop bits (BACnet)
  • 1
  • Stop bits (ModBus)
  • 1-2
  • Parity (BACnet)
  • non
  • Parity
  • non-pair-impar (Modbus)
  • Protocol
  • ModBus/BACnet
  • Speed
  • 9600-19200-38400-57600-76800-115200
  • USER INTERFACE
  • Display format
  • 4:3
  • LED
  • 3 LED (CPU-Keys-ALARM)
  • Resolution of the display
  • VGA (640×480)
  • Keyboard
  • Capacitive, 3 keys
  • Display type
  • TFT color
  • Visible display area size
  • 5″
  • DIGITAL INPUTS
  • Input/output insulation
  • 4 kV
  • Quantity
  • 2
  • Type
  • Potential-free contact
  • Maximum short-circuit current
  • 5 mA
  • Maximum open circuit voltage
  • 15 Vdc
  • DIGITAL RELAY OUTPUTS
  • Electrical life (at maximum load)
  • 3×104cycles
  • Mechanical life
  • 1×107cycles
  • Maximum switching capacity
  • 1500 VA
  • DIGITAL TRANSISTOR OUTPUTS
  • Pulse width
  • 1 ms
  • Quantity
  • 2
  • Type
  • NPN
  • Pulse output, time period (Ton / Toff)
  • 0,3 ms/0,7 ms
  • Maximum frequency
  • 1 kHz
  • Maximum current
  • 130 mA
  • Maximum voltage
  • 48 Vdc
  • MEASUREMENT ACCURACY
  • Frequency measurement
  • Class 0.1 (…/5A, …/1A, …/0.250A)
  • Phase current measurement
  • Class 0.2 ±1 digit 0.05…8A (…/5A),0.01…1.2A (…/1A),0.01…0.3A (…/0.250A)
  • Neutral current measurement
  • class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), calculated (…/0.250A)
  • Reactive energy measurement (kvarh)
  • (IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
  • Reactive power measurement (kvar)
  • (Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
  • Apparent power measurement (kVA)
  • (Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
  • Active energy measurement (kWh)
  • (IEC 62053-22) Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
  • Power factor measurement
  • class 0,5 (…/5A, …/1A, …/0.250A)
  • Current THD
  • class 1 (…/5A, …/1A, …/0.250A)
  • Voltage THD
  • class 1 (…/5A, …/1A, …/0.250A)
  • Phase voltage measurement
  • class 0.2 ±1 digit (20…600 V~, …/5A, …/1A, …/0.250A)
  • Neutral voltage measurement
  • Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
  • Current harmonics (THD)
  • class 1 (…/5A, …/1A, …/0.250A)
  • Voltage harmonics (THD)
  • class 1 (…/5A, …/1A, …/0.250A)

 

Reviews

There are no reviews yet.

Be the first to review “CVM-B100-ITF-485-ICT2”

Your email address will not be published. Required fields are marked *