Description
CVM-B150-ITF-485-ICT2, Power analyzer
Code: M56111.
- Protocol: Modbus/RTU | BACnet
- Energy accuracy: 0,5 S (…/5A)
- Communications: RS-485
- Transistor output: 2
- Nº relays: 2
- Digital inputs: 2
- Input current: …/5 A | …/1 A | …/250 mA
- Mounting: Pannel
- Modules: 144 x 144
INFORMATION
DESCRIPTION
The CVM-B100 and CVM-B150 units are panel mounted three-phase power analyzers (dimensions: 96×96 and 144×144 mm, respectively). Both offer 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phase circuits or ARON connections.
The CVM-B100 and CVM-B150 high-performance units feature a measurement engine that allows the user to analyse many different electrical parameters, in addition to offering a large variety of optional expansion modules for the same unit.
Features:
- Format: 96×96 (CVM B100) and 144×144 (CVM B150)
- High-resolution VGA colour screen
- IP 65 front panel protection (with sealing joint)
- 5 voltage inputs (3 phases + neutral + earth) 1000 Vf-f
- 4 Current inputs, ITF
- Class 0.2 voltage and current accuracy
- Class 0.5S energy accuracy
- Expandable unit, up to 4 modules, combining digital and analogue outputs, Modbus/TCP, MBus, LonWorks, Profibus, XML/Web
- Modular (optional addition of expansion modules)
- Touch-sensitive movement buttons
- Universal power supply source
- RS485 communications port (Modbus/RTU and BACnet protocols)
- Customisation of parameters to be displayed
- Operating hour indicator for preventive maintenance.
Other features:
- Innovative SCV interface (Slide, Choose & View) for versatile data display, enabling the customisation of the parameters displayed on the screen
- Electrical parameters: instantaneous, maximum, minimum (with date and time) and demand
- Incremental electrical parameters (energy), times, costs, emissions
- 3 Tariffs (can be selected via the digital input or RS485 communications)
- Capable of showing costs and kgCO2 emission sources on the screen, depending on the energy consumed or generated
- 2 Relay outputs for alarms with delay, times, ON and OFF, etc.
- 2 transistor outputs for alarms or impulse generation, with all the possible configuration parameters
- 2 digital inputs, with control over the selection of the unit’s tariffs or configurable for monitoring purposes, with RS-485 Modbus communications, monitoring of logical states of other electromechanical units. (RCCBs, thermal-magnetic circuit breakers, etc.)
APPLICATIONS
- Control and monitoring of all electrical parameters measured in any electric distribution panel and low and high-voltage connection points.
- 4 alarms (2 per transistor and 2 per relay), fully and independently programmable: low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
- Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2, total meter or tariff hours)
- Transducer that converts analogue signals to any instantaneous parameter that the unit can measure or calculate, with built-in expansion modules with analogue outputs.
- Display of process signals, with a built-in expansion module with analogue inputs; optional reporting of these signals to SCADA systems through communication systems
- Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
- Autonomous datalogger with web server, connected to a M-CVMAB-Datalogger module. Enables direct monitoring of the historical data stored in the unit via a conventional web browser.
400 Hz Applications
CVM-B150 provides a version adapted to 400 Hz networks specially designed for applications such as:
- Aeronautical
- Astronautics
- Naval
- Military
- SPECIFICATIONS
- AC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- máx. 29.4 VA
- Frequency
- 45 … 65Hz
- Nominal voltage
- 100 … 240 V ~
- DC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 11.9 W
- Nominal voltage
- 120 … 300 Vdc
- MECHANICAL CHARACTERISTICS
- Size (mm) width x height x depth
- 144 x 144 x 96 (mm)
- Envelope
- Self-extinguishing V0 plastic
- Fastening
- Panel 138×138
- Weight (kg)
- 0,704
- ENVIRONMENTAL CHARACTERISTICS
- Protection class
- IP 40 (Front), IP 65 (Sealing), IP 30 (unmounted)
- Relative humidity (without condensation)
- 5 … 95%
- Storage temperature
- -20… +80 ºC
- Working temperature
- -10…+60 ºC
- STANDARDS
- Certifications
- UL 61010-1 3rd edition, CAN/CSA-C22.2 No.61010-1 3rd. edition 2012-05
- Electrical safety, Maximum height (m)
- 2000
- Standards
- IEC 61010-1 (1rd. Edition), UNE-EN 61000-6-2, UNE-EN 61000-6-4, IEC 60664-1, IEC 61010-2-030 (First Edition). Measurement according to IEC 61557-12
- CURRENT MEASUREMENT CIRCUIT
- Installation category
- CAT III 600 V
- Nominal current (In)
- …/5A, …/1A, …/0.250A
- Phase current measuring range
- 01…10A (…/5A),0.01…2A (…/1A), 0.01…0.5A (…/0.250A)
- Neutral current measuring range
- 02…0.5A (…/0.250A, calculated)
- Maximum input current consumption
- 0,9 VA
- Maximum pulse current
- 100 A
- Minimum current measurement
- 0,01 A (…/5A, …/1A, …/0,250A
- VOLTAGE MEASUREMENT CIRCUIT
- Installation category
- CAT III 600V
- Input impedance
- 2MΩ
- Frequency measuring range
- 40…70Hz
- Voltage measuring range
- 20…600 V~
- Maximum input voltage consumption
- 0,15VA
- Minimum measurement voltage (Vstart)
- 10 V~
- COMMUNICATIONS
- Fieldbus (BACnet)
- MS/TP
- Fieldbus (ModBus)
- RS-485 / RTU
- Stop bits (BACnet)
- 1
- Stop bits (ModBus)
- 1-2
- Parity (BACnet)
- non
- Parity
- non-pair-impar (Modbus)
- Protocol
- ModBus/BACnet
- Speed
- 9600-19200-38400-57600-76800-115200
- USER INTERFACE
- Display format
- 4:3
- LED
- 3 LED (CPU-Keys-ALARM)
- Resolution of the display
- VGA (640×480)
- Keyboard
- Capacitive, 3 keys
- Display type
- TFT color
- Visible display area size
- 6″
- DIGITAL INPUTS
- Input/output insulation
- 4 kV
- Quantity
- 2
- Type
- Potential-free contact
- Maximum short-circuit current
- 5 mA
- Maximum open circuit voltage
- 15 Vdc
- DIGITAL RELAY OUTPUTS
- Electrical life (at maximum load)
- 3×104cycles
- Mechanical life
- 1×107cycles
- Maximum switching capacity
- 1500 VA
- DIGITAL TRANSISTOR OUTPUTS
- Pulse width
- 1 ms
- Quantity
- 2
- Type
- NPN
- Pulse output, time period (Ton / Toff)
- 0,3 ms/0,7 ms
- Maximum frequency
- 1 kHz
- Maximum current
- 130 mA
- Maximum voltage
- 48 Vdc
- MEASUREMENT ACCURACY
- Frequency measurement
- Class 0.1 (…/5A, …/1A, …/0.250A)
- Phase current measurement
- Class 0.2 ±1 digit 0.05…8A (…/5A),0.01…1.2A (…/1A),0.01…0.3A (…/0.250A)
- Neutral current measurement
- class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), calculated (…/0.250A)
- Reactive energy measurement (kvarh)
- (IEC 62053-23) Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
- Reactive power measurement (kvar)
- (Vn 230/110 Vac) Class 1 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
- Apparent power measurement (kVA)
- (Vn 230/110 Vac) class 0.5 ±1 digit 0.05…6A (…/5A),0.01…1.2A ( …/1A), 0.01…0.3A (…/0.250A)
- Active energy measurement (kWh)
- (IEC 62053-22) Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
- Power factor measurement
- class 0,5 (…/5A, …/1A, …/0.250A)
- Current THD
- class 1 (…/5A, …/1A, …/0.250A)
- Voltage THD
- class 1 (…/5A, …/1A, …/0.250A)
- Phase voltage measurement
- class 0.2 ±1 digit (20…600 V~, …/5A, …/1A, …/0.250A)
- Neutral voltage measurement
- Class 0.5 ±1 digit (50…600 Vca, …/5A, …/1A, …/0.250A)
- Current harmonics (THD)
- class 1 (…/5A, …/1A, …/0.250A)
- Voltage harmonics (THD)
- class 1 (…/5A, …/1A, …/0.250A)
Reviews