CVM-C4-ITF-485-ICT2

Compare
Category:

Description

CVM-C4-ITF-485-ICT2, Power analizer, panel mounted 96×96

Code: M52706.

  • Protocol: Modbus/RTU
  • Communications: RS-485
  • Transistor output: 2
  • Nº relays: 2
  • Digital inputs: 2
  • Measuring current Channels: 3
  • Input current: …/5 A | …/1 A
  • Mounting: Pannel

 

INFORMATION

DESCRIPTION

CVM-C4 is a power analyser that measures, calculates and displays the main electrical parameters for single-phase and three-phase networks (with or without neutral) on its screen. Measurement is made in true rms value, by means of 3 AC voltage inputs and 3 /5 A or /1 A current inputs. Relay outputs enable local operation in the event of an alarm event being triggered. Its dimensions are 96 x 96 mm with a depth of only 41.5 mm. Current measurement is indirectly carried out by /5A or /1A transformers. It allows AC (80…270 Vac)and DC (80…270 Vdc or 18… 36 Vdc power supply systems). It features RS-485 communications enabling remote data readout or Scada or Master centralisation.

APPLICATIONS

  • For electrical parameter measurement in areas whose reduced dimensions require the installation of a space-saving panel analyser.
  • Instantaneous value measurement of electrical parameters with communications.
  • Logging of consumed or generated Active or Reactive Energy.
  • The device’s relay outputs allow the installation to be locally operated.
  • Programmable alarms by setting relay activation time, connection delay and hysteresis.
  • 5000 imp/kWh energy impulse outputs
  • Energy measurement of two different sources on 2 separate meters (by digital input activation).
  • Voltage and current THD% measurement to check for harmonics in the installation.
  • SPECIFICATIONS
  • AC POWER SUPPLY
  • Installation category
  • CAT III 300V
  • Consumption
  • 6 … 18 VA
  • Frequency
  • 50/60 Hz
  • Nominal voltage
  • 80 … 270 Vac
  • DC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 5 … 1.8 W
  • Nominal voltage
  • 80…270 Vdc
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 96 x 96 x 41.5 (mm)
  • Envelope
  • Polycarbonate + ABS
  • Torque setting
  • 5 Nm
  • Communications cable cross-section
  • 5 mm2
  • Cable gauge at power supply terminals
  • 5 mm2
  • Cable gauge at input and output terminals
  • 2,5 mm 2
  • Cable gauge at current terminals
  • 2,5 mm2
  • Cable gauge at voltage terminals
  • 5 mm2
  • Weight (kg)
  • 0,268
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • Front: IP54, Rear: IP20
  • Relative humidity (without condensation)
  • 5 … 95%
  • Storage temperature
  • -20 … +70 ºC
  • Working temperature
  • -10 … +60 ºC
  • CURRENT MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Consumption
  • < 0.2 VA (por fase)
  • Nominal current (In)
  • 1 A / 5 A ~
  • Allowable overload
  • 2 In continuous, 10 In instantaneous(5s)
  • VOLTAGE MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Consumption
  • < 0.2 VA (por fase)
  • Sampling frequency
  • 45…65 Hz
  • Input impedance
  • > 1.7 MΩ
  • Nominal voltage
  • 100…277 V~ Ph-N (± 8%)
  • Maximum permanent measurement voltage
  • 2 Un continous, 2 Un instantaneous
  • COMMUNICATIONS
  • Data bits
  • 8
  • Stop bits (ModBus)
  • 1-2
  • Parity
  • non-pair-impar
  • Protocol
  • ModBus RTU
  • Speed
  • 2400-4800-9600-19200
  • STANDARDS
  • Electrical safety, Maximum height (m)
  • 2000
  • Electrical safety, Installation category
  • CAT III 300 V
  • Electrical safety, Contamination level/class
  • Pollution resistance 2
  • Standards
  • IEC 61010-1, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEC 61000-4-11
  • USER INTERFACE
  • Keyboard
  • 3 keys
  • Display type
  • LCD
  • DIGITAL INPUTS
  • Input/output insulation
  • 3,75 kV RMS
  • Quantity
  • 2
  • Type
  • Potential-free contact
  • Maximum short-circuit current
  • 4 mA
  • Maximum open circuit voltage
  • 30 V
  • DIGITAL RELAY OUTPUTS
  • Quantity
  • 2
  • Type
  • Relay
  • Resistive load (max.)
  • 250 Vca / 5 Aca, 30 Vcc / 5 Acc
  • Maximum current
  • 5 A ~
  • Maximum open contact voltage
  • 277 V ~ / 30 Vdc
  • Electrical life
  • (250 V ~ / 5 A) 1 x 105
  • Maximum switching capacity
  • 1385 VA / 150 W
  • DIGITAL TRANSISTOR OUTPUTS
  • Pulse width
  • Minimum pulse width: 80mA
  • Type
  • Passive impulse
  • Maximum frequency
  • 10 Hz
  • Maximum current
  • 27 mA
  • Maximum voltage
  • 27 Vcc
  • MEASUREMENT ACCURACY
  • Frequency measurement
  • 5 %
  • Phase current measurement
  • 2 %
  • Reactive energy measurement (kvarh)
  • 5 %
  • Reactive power measurement (kvar)
  • 5 %
  • Active energy measurement (kWh)
  • 5 %
  • Active power measurement (kW)
  • 5 %
  • Phase voltage measurement
  • 2 %

 

Reviews

There are no reviews yet.

Be the first to review “CVM-C4-ITF-485-ICT2”