CVM-E3-MINI-ITF-485-IC

Compare
Category:

Description

CVM-E3-MINI-ITF-485-IC, Power analyzer

Code: M56414.

  • Protocol: Modbus/RTU | BACnet
  • Communications: RS-485
  • Transistor output: 1
  • Digital inputs: 1
  • Harmonics: 31
  • Power supply (Vac): 207…253 Vac
  • Input current: …/5 A | …/1 A
  • Mounting: DIN rail

 

INFORMATION

DESCRIPTION

Three-phase power analyzer (balanced and unbalanced) for mounting on DIN rail, very compact, with measurements in 4 quadrants.

Other features:

  • Current measurement …/5 or …/1 A or …/250 mA or Rogowski type sensors
  • With ITF technology: ITF galvanic insulation protection
  • DIN rail with only 3 modules
  • High-contrast backlit display
  • 72 x 72 mm panel mounting with front adapter
  • RS-485 communication (Modbus/RTU up to 19.2 kbps) (Bacnet up to 19.2 kbps)
  • One transistor output (programmable)
  • One digital input for selecting tariff or logic states
  • Sealable terminal cover
  • Harmonic display (V, A) up to 31º

APPLICATIONS

  • Control application in low- and medium-voltage distribution panels and switchboards where it is necessary to place an analyzer on the DIN rail due to problems of space.
  • Alarm control. Maximum value, minimum value and programmable delay.
  • Control of active or reactive energy by impulse output.
  • Capture of maximum and minimum instantaneous data of electrical parameters measured.
  • SPECIFICATIONS
  • AC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 4 VA
  • Frequency
  • 50…60 Hz
  • Nominal voltage
  • 207…253 Vc.a.
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 5 x 118 x 74 (mm)
  • Envelope
  • Self-extinguishing V0 plastic
  • Differential current measurement
  • 2,5 mm2
  • Cable gauge at power supply terminals
  • 1 mm2 (min.)
  • Cable gauge at voltage terminals
  • mín. 1 mm2
  • Fastening
  • DIN rail
  • Weight (kg)
  • 0,38
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • IP 30 / Front: IP 40
  • Relative humidity (without condensation)
  • 5…95%
  • Storage temperature
  • -10 … +50 ºC
  • Working temperature
  • -5 … +45 ºC
  • CURRENT MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Nominal current (In)
  • …/5 A ó …/1 A
  • Phase current measuring range
  • 2…120% de In
  • Maximum input current consumption
  • 0,9 VA
  • Minimum current measurement
  • 0,2 % In
  • VOLTAGE MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Input impedance
  • 400 kΩ
  • Frequency measuring range
  • 45…65 Hz
  • Voltage measuring range
  • 5 … 120 % Un
  • Nominal voltage
  • 300V Ph-N, 520V Ph-Ph
  • Minimum measurement voltage (Vstart)
  • 11 V Ph-N
  • COMMUNICATIONS
  • Fieldbus (BACnet)
  • MS/TP
  • Fieldbus (ModBus)
  • RS-485
  • Stop bits (BACnet)
  • 1
  • Stop bits (ModBus)
  • 1-2
  • Parity (BACnet)
  • non
  • Parity
  • non-pair-impar
  • Protocol
  • ModBus/RTU, BACnet
  • Speed
  • ModBus RTU: 9600-19200 bps / BACnet: 9600-19200 bps (38400-57600-115200 bps: Available on devices with software V2.xx)
  • STANDARDS
  • Electrical safety, Maximum height (m)
  • 2000
  • Standards
  • IEC 61010-1, IEC 61010-2-030, IEC 61326-1, IEC 61557-12 , UL94
  • USER INTERFACE
  • LED
  • 2 LED
  • Keyboard
  • 3 keys
  • Display type
  • LCD Custom COG
  • DIGITAL INPUTS
  • Input/output insulation
  • Optoisolated
  • Quantity
  • 1
  • Type
  • NPN Potential-free contact
  • DIGITAL TRANSISTOR OUTPUTS
  • Pulse width
  • 30…500 ms (Programmable)
  • Type
  • NPN
  • Maximum frequency
  • 16 imp / s
  • Maximum current
  • 50 mA
  • Maximum voltage
  • 24 Vdc
  • MEASUREMENT ACCURACY
  • Frequency measurement
  • 0,50%
  • Phase current measurement
  • 0,5% ± 1 digit
  • Reactive energy measurement (kvarh)
  • Class 2
  • Reactive power measurement (kvar)
  • class 2
  • Apparent power measurement (kVA)
  • 5 % ±2 digits
  • Active energy measurement (kWh)
  • I < 0,1 In (Class 1) / I > 0,1 In (Class 0,5)
  • Active power measurement (kW)
  • 5 % ±2 digits
  • Phase voltage measurement
  • 5% ± 1 digit

 

Reviews

There are no reviews yet.

Be the first to review “CVM-E3-MINI-ITF-485-IC”

Your email address will not be published. Required fields are marked *