Description
CVM-E3-MINI-ITF-485-IC, Power analyzer
Code: M56414.
- Protocol: Modbus/RTU | BACnet
- Communications: RS-485
- Transistor output: 1
- Digital inputs: 1
- Harmonics: 31
- Power supply (Vac): 207…253 Vac
- Input current: …/5 A | …/1 A
- Mounting: DIN rail
INFORMATION
DESCRIPTION
Three-phase power analyzer (balanced and unbalanced) for mounting on DIN rail, very compact, with measurements in 4 quadrants.
Other features:
- Current measurement …/5 or …/1 A or …/250 mA or Rogowski type sensors
- With ITF technology: ITF galvanic insulation protection
- DIN rail with only 3 modules
- High-contrast backlit display
- 72 x 72 mm panel mounting with front adapter
- RS-485 communication (Modbus/RTU up to 19.2 kbps) (Bacnet up to 19.2 kbps)
- One transistor output (programmable)
- One digital input for selecting tariff or logic states
- Sealable terminal cover
- Harmonic display (V, A) up to 31º
APPLICATIONS
- Control application in low- and medium-voltage distribution panels and switchboards where it is necessary to place an analyzer on the DIN rail due to problems of space.
- Alarm control. Maximum value, minimum value and programmable delay.
- Control of active or reactive energy by impulse output.
- Capture of maximum and minimum instantaneous data of electrical parameters measured.
- SPECIFICATIONS
- AC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 4 VA
- Frequency
- 50…60 Hz
- Nominal voltage
- 207…253 Vc.a.
- MECHANICAL CHARACTERISTICS
- Size (mm) width x height x depth
- 5 x 118 x 74 (mm)
- Envelope
- Self-extinguishing V0 plastic
- Differential current measurement
- 2,5 mm2
- Cable gauge at power supply terminals
- 1 mm2 (min.)
- Cable gauge at voltage terminals
- mín. 1 mm2
- Fastening
- DIN rail
- Weight (kg)
- 0,38
- ENVIRONMENTAL CHARACTERISTICS
- Protection class
- IP 30 / Front: IP 40
- Relative humidity (without condensation)
- 5…95%
- Storage temperature
- -10 … +50 ºC
- Working temperature
- -5 … +45 ºC
- CURRENT MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Nominal current (In)
- …/5 A ó …/1 A
- Phase current measuring range
- 2…120% de In
- Maximum input current consumption
- 0,9 VA
- Minimum current measurement
- 0,2 % In
- VOLTAGE MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Input impedance
- 400 kΩ
- Frequency measuring range
- 45…65 Hz
- Voltage measuring range
- 5 … 120 % Un
- Nominal voltage
- 300V Ph-N, 520V Ph-Ph
- Minimum measurement voltage (Vstart)
- 11 V Ph-N
- COMMUNICATIONS
- Fieldbus (BACnet)
- MS/TP
- Fieldbus (ModBus)
- RS-485
- Stop bits (BACnet)
- 1
- Stop bits (ModBus)
- 1-2
- Parity (BACnet)
- non
- Parity
- non-pair-impar
- Protocol
- ModBus/RTU, BACnet
- Speed
- ModBus RTU: 9600-19200 bps / BACnet: 9600-19200 bps (38400-57600-115200 bps: Available on devices with software V2.xx)
- STANDARDS
- Electrical safety, Maximum height (m)
- 2000
- Standards
- IEC 61010-1, IEC 61010-2-030, IEC 61326-1, IEC 61557-12 , UL94
- USER INTERFACE
- LED
- 2 LED
- Keyboard
- 3 keys
- Display type
- LCD Custom COG
- DIGITAL INPUTS
- Input/output insulation
- Optoisolated
- Quantity
- 1
- Type
- NPN Potential-free contact
- DIGITAL TRANSISTOR OUTPUTS
- Pulse width
- 30…500 ms (Programmable)
- Type
- NPN
- Maximum frequency
- 16 imp / s
- Maximum current
- 50 mA
- Maximum voltage
- 24 Vdc
- MEASUREMENT ACCURACY
- Frequency measurement
- 0,50%
- Phase current measurement
- 0,5% ± 1 digit
- Reactive energy measurement (kvarh)
- Class 2
- Reactive power measurement (kvar)
- class 2
- Apparent power measurement (kVA)
- 5 % ±2 digits
- Active energy measurement (kWh)
- I < 0,1 In (Class 1) / I > 0,1 In (Class 0,5)
- Active power measurement (kW)
- 5 % ±2 digits
- Phase voltage measurement
- 5% ± 1 digit
Reviews