CVM k2-ITF-405

Compare
Category:

Description

CVM k2-ITF-405, Analyzer

Code: M54400.

  • Protocol: Modbus/RTU
  • Communications: RS-485
  • Class in power: 0.5

 

 

INFORMATION

DESCRIPTION

Three-phase power analyzer (balanced and unbalanced networks), assembly on panels or DIN rails, with a graphical display, with 4-quadrant measurement.

Other features include:

  • Class 0.2 or 0.5 power and energy
  • Measurement of power quality events (guaranteeing the power supply of the unit by means of a UPS system, battery, etc.)
  • Current measurement …/5 or …/1 A
  • Measurement of the neutral current with a transformer
  • Rating of consumed and generated energy (up to 9 tariffs)
  • RS-485 Modbus/RTU communication
  • Possibility of expansion (up to 3 modules)
  • Backlit VGA graphic screen
  • Instantly shows electrical parameters, maximum and minimum values with date and time
  • Consumed and generated energy meter up to 100 GW·h
  • Universal power supply as standard
  • With ITF technology: galvanic insulation protection

APPLICATIONS

  • Control application for general distribution switchboards and low-, medium- and high-voltage connection points
  • Alarm station, featuring voltage-free digital inputs
  • Submetering station: impulse meter for other services (gas, water, steam etc.) via the digital inputs
  • Measurement transducer: possibility of associating instantaneous parameters with one of the available analogue outputs (0 to 20 mA / 4 to 20 mA)
  • Unit for recording the instantaneous, maximum and minimum parameters, with date and time, via the memory expansion card
  • Power quality analyzer: Harmonic decomposition, up to the 50th order harmonic, asymmetries, flicker, unbalances, overvoltages, gaps, interruptions, etc.
  • SPECIFICATIONS
  • AC POWER SUPPLY
  • Installation category
  • CAT III 300/520 Vac (IEC 61010)
  • Consumption
  • <30 VA
  • Frequency
  • 50…60Hz
  • Nominal voltage
  • 85…265 Vc.a. (-15…+10%)
  • DC POWER SUPPLY
  • Consumption
  • <25 W
  • Nominal voltage
  • 100…300 Vdc
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 144 x 144 x 116 (mm)
  • Envelope
  • Self-extinguishing V0 plastic
  • Cable gauge at power supply terminals
  • 1 mm2(mín)
  • Cable gauge at current terminals
  • 2,5 mm2
  • Cable gauge at voltage terminals
  • 1 mm2
  • Weight (kg)
  • 0,81
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • IP 51 (Front), IP 20 (rear)
  • Relative humidity (without condensation)
  • 5…95%
  • Storage temperature
  • -20…+65 ºC
  • Working temperature
  • -10…+50 ºC
  • STANDARDS
  • Certifications
  • CE, UL, VDE
  • Electrical safety, Maximum height (m)
  • 2000
  • Electrical safety, Installation category
  • CAT III 300V / 520V, IEC 61010
  • Standards
  • IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 55011, IEC 62053-22
  • CURRENT MEASUREMENT CIRCUIT
  • Nominal current (In)
  • In/5A, In/1A
  • Primary current measurement
  • Programmable < 30000 A
  • Phase current measuring range
  • 1…120% In (In = 5 A)
  • Permanent overload
  • 2 In
  • Maximum input current consumption
  • <0,45 VA (…/5 , …/1)
  • Maximum pulse current
  • 100 A
  • Minimum current measurement
  • 40 mA
  • VOLTAGE MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300/520 V (EN-61010)
  • Frequency measuring range
  • 45…65 Hz
  • Voltage measuring range
  • 5 …120% Un
  • Nominal voltage
  • 300V Ph-N, 520V Ph-Ph
  • Maximum input voltage consumption
  • <0,6 VA
  • Minimum measurement voltage (Vstart)
  • 10 V~
  • COMMUNICATIONS
  • Fieldbus
  • RS-485 / Ethernet RJ-45
  • Stop bits (ModBus)
  • 1 – 2
  • Parity
  • non-pair-impar
  • Protocol
  • ModBus/RTU, ModBus/TCP
  • Speed
  • 9600 – 19200 – 38400 – 57600 / Ethernet: 10baseT / 100base /Tx compatible
  • Peripheral number
  • 1…255
  • ELECTRICAL SAFETY
  • Insulation
  • Double-insulated electric shock protection class II (IEC 61010-1)
  • DIGITAL INPUTS
  • Consumption (per input)
  • <0,5 W
  • Minimum signal width
  • 40 ms
  • Operating voltage
  • 24 Vdc ± 20 %
  • ANALOGUE OUTPUTS
  • Current mode, nominal range
  • 0-20 mA/4-20 mA
  • Current mode: maximum load resistance
  • 300 Ω
  • DAC resolution
  • 4000 points
  • Response time
  • < 2 s
  • DIGITAL TRANSISTOR OUTPUTS
  • Type
  • Optocoupler
  • Maximum current
  • 100 mA
  • Maximum resistance RON
  • 25 Ω
  • Maximum voltage
  • 150 Vdc / 250 V~
  • MEASUREMENT ACCURACY
  • Power factor measurement
  • 0,5…1
  • Phase voltage measurement
  • ± 0,5% ± 1 (20 … 120% Un)

 

Reviews

There are no reviews yet.

Be the first to review “CVM k2-ITF-405”

Your email address will not be published. Required fields are marked *