Description
CVM-MINI-MC-ITF-RS485-C2, Power analyzer
Code: M52081.
- Protocol: Modbus/RTU
- Insulated input: Yes
- Communications: RS-485
- Transistor output: 2
- Input current: …/250 mA
- Mounting: DIN rail
INFORMATION
DESCRIPTION
Three-phase power analyzer (balanced and unbalanced), assembly on DIN rail, with a very compact size, and 4-quadrant measurement.
Other features include:
- Current measurement …/5 or …/1 A or …/250 mA, …/333 mV
- DIN rail format of only 3 modules
- Assembly on 72 x 72 mm panel with adapter front panel
- RS-485 Communications (Modbus-RTU) depending on model
- It features two transistor outputs (programmable)
- With ITF technology: galvanic insulation protection, depending on the type
- Selection of parameters to display
- Selection of the default page
- Universal power supply (optional)
- Sealable
APPLICATIONS
- Control application on switchboards and low and medium voltage connection points, where an analyzer must be installed on a DIN rail due to space restrictions.
- Alarm control. Maximum value, minimum value and programmable delay.
- Control of active or reactive energy using the impulse output.
- Instantaneous data capture, maximum and minimum values of the electrical parameters measured.
- SPECIFICATIONS
- AC POWER SUPPLY
- Consumption
- 3 VA
- Frequency
- ..60 Hz
- Nominal voltage
- 230 Vc.a.(-15…+10%)
- MECHANICAL CHARACTERISTICS
- Size (mm) width x height x depth
- 53 x 85 x 85 (mm)
- Envelope
- Self-extinguishing V0 plastic
- Fastening
- DIN rail 46227
- Weight (kg)
- 0,178
- ENVIRONMENTAL CHARACTERISTICS
- Protection class
- IP 51 (Front), IP 31 (unmounted)
- Relative humidity (without condensation)
- 5…95%
- Working temperature
- -10…+50 ºC
- STANDARDS
- Certifications
- CE, UL, VDE
- Electrical safety, Maximum height (m)
- 2000
- Electrical safety, Installation category
- CAT III 300V / 520V, IEC 61010
- Standards
- IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3, EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 55011
- CURRENT MEASUREMENT CIRCUIT
- Nominal current (In)
- In/250 mA
- Phase current measuring range
- 0,2%…120% (ITF)
- Permanent overload
- 2 In
- Maximum input current consumption
- 0,18 VA
- VOLTAGE MEASUREMENT CIRCUIT
- Frequency measuring range
- 45 … 65 Hz
- Nominal voltage
- 300V Ph-N, 520V Ph-Ph
- Maximum input voltage consumption
- 0,7 VA
- COMMUNICATIONS
- Stop bits (ModBus)
- 1-2
- Parity
- non-pair-impar
- Protocol
- ModBus RTU
- Speed
- 1200-2400-4800-9600-19200
- Peripheral number
- 0…255
- ELECTRICAL SAFETY
- Insulation
- Double-insulated electric shock protection class II (IEC 61010-1)
- DIGITAL TRANSISTOR OUTPUTS
- Pulse width
- 100 ms
- Quantity
- 2
- Type
- NPN
- Maximum frequency
- 5 imp / s
- Maximum current
- 50 mA
- Maximum voltage
- 24 Vdc
- MEASUREMENT ACCURACY
- Current measurement sensors
- External transformers
- Voltage measurement sensors
- Direct voltage
- Power factor measurement
- 0,5…1
- Phase voltage measurement
- 5% ± 1 digit
Reviews