Description

CVM-NET4+-ITF-MC-RS485-C4, Power analyzer

Code: M55782.

  • Protocol: Modbus/RTU
  • Communications: RS-485
  • Transistor output: 4
  • Harmonics: 15
  • Input current: …/250 mA
  • Mounting: DIN rail

INFORMATION

DESCRIPTION

CVM-NET4+ is a multi-channel power analyzer designed to measure balanced or unbalanced three-phase networks and to measure single-phase networks. Its versatile configuration options enable you to take measurements in single-phase systems, three-phase systems or a combination of both. It has a single three-phase voltage input combined with 12 single-phase channels to measure the current from the MC efficient current transformers.

Its main features include:

  • Assembly on DIN rail
  • Compact size (6 DIN rail modules)
  • Measurement of up to 12 single-phase channels or combined single-phase and three-phase current channels.
  • Current measurement using efficient MC series transformers (…/250 mA)
  • RS-485 Communications (Modbus/RTU)
  • 4 programmable digital outputs for alarms or impulses
  • Compatible with PowerStudio /PowerStudio Scada / PowerStudio Scada Deluxe

APPLICATIONS

  • Measurement of electrical parameters in multi-channel installations, such as data processing centres and switchboards of single-phase loads.
  • Simultaneous measurement at 4 different points in three-phase installations
  • Its compact size is perfect for assembly on electric panels.
  • SPECIFICATIONS
  • AC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 6 VA
  • Frequency
  • 50…60Hz
  • Nominal voltage
  • 85…265 Vc.a.
  • DC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 6 W
  • Nominal voltage
  • 95…300 Vdc
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 105 x 90 x 70 (mm)
  • Envelope
  • Self-extinguishing V0 plastic
  • Fastening
  • DIN rail 46227 (EN 50022)
  • Weight (kg)
  • 0,234
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • IP 51 (Front), IP 31 (unmounted)
  • Relative humidity (without condensation)
  • 5…95%
  • Working temperature
  • -10…+50 ºC
  • STANDARDS
  • Certifications
  • UL, VDE
  • Electrical safety, Maximum height (m)
  • 2000
  • Electrical safety, Installation category
  • CAT III 300V / 520V, IEC 61010
  • Standards
  • IEC 664, VDE 0110, UL 94, IEC 801, IEC 348, IEC 571-1, EN 61000-6-3,EN 61000-6-1, EN 61010-1, EN 61000-4-11, EN 61000-4-3, EN 61000-4-3,EN 61000-4-4, EN 61000-4-5, EN 55011
  • CURRENT MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Nominal current (In)
  • …/250 mA
  • Phase current measuring range
  • 0…250 mA
  • Permanent overload
  • 3 In
  • Maximum input current consumption
  • 0,18 VA x 4 channels
  • Maximum pulse current
  • In x 1.3
  • Minimum current measurement
  • 3 mA
  • VOLTAGE MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Input impedance
  • 4 MΩ
  • Frequency measuring range
  • 45 … 65 Hz
  • Nominal voltage
  • 300V Ph-N, 520V Ph-Ph
  • Maximum input voltage consumption
  • 0,7 VA
  • Minimum measurement voltage (Vstart)
  • 5 V~
  • COMMUNICATIONS
  • Fieldbus
  • RS-485
  • Stop bits (ModBus)
  • 1
  • Parity
  • non
  • Protocol
  • ModBus RTU
  • Speed
  • 9600 – 19200 – 38400 – 57600
  • ELECTRICAL SAFETY
  • Insulation
  • Double-insulated electric shock protection class II (IEC 61010-1)
  • DIGITAL TRANSISTOR OUTPUTS
  • Pulse width
  • 100 ms
  • Quantity
  • 4
  • Type
  • NPN
  • Maximum frequency
  • 5 imp / s
  • Maximum current
  • 50 mA
  • Maximum voltage
  • 24 Vdc
  • MEASUREMENT ACCURACY
  • Current measurement sensors
  • External transformers
  • Voltage measurement sensors
  • Direct voltage
  • Phase voltage measurement
  • 0,50%

 

Reviews

There are no reviews yet.

Be the first to review “CVM-NET4+-ITF-MC-RS485-C4”

Your email address will not be published. Required fields are marked *