Description
Line-CVM-D32, Power analyzer
Code: M58100.
- Protocol: Modbus/RTU
- Communications: RS-485 | Bus-Line
- Transistor output: 2
- Measuring current Channels: 3
- Harmonics: 40
- Input current: …/5 A | …/1 A | …/250 mA
- Mounting: DIN rail
INFORMATION
DESCRIPTION
The Line-CVM-D32 is a power analyser that measures, calculates and displays the main electrical parameters in single-phase networks, in systems with two phases without ground, with ARON connections or balanced or unbalanced three-phase systems. The measurement is a true RMS that relies on 3 AC voltage inputs and 3 current inputs. The device is modular and scalar thanks to expansion modules with different functionalities. The current is measured indirectly using /5A, /1A or /250mA transformers The voltage is measured directly in networks of up to 300V ~ P-N or through voltage transformers. Supply quality events counter (Overvoltages, gaps and interruptions)
APPLICATIONS
- Measurement of electrical parameters in switchboards and low- and medium-voltage connections where space constraints require installing a space-saving analyser in the DIN rail.
- Measurement of instantaneous, maximum and minimum values of electrical parameters.
- Logging of consumed or generated Active or Reactive Energy.
- Pricing of electricity in up to 4 tariffs (via communications or expansion module inputs)
- Generation of impulses through outputs to a transistor, fully and independently configurable based on any incremental parameter of active or reactive energy, either per total counter or per tariff.
- The installation can be controlled by way of programmable timer on delay, timer off delay and interlock alarms.
- Ability to expand the analyser’s features by using expansion modules with transistor, relay or analogue inputs/outputs.
- Convert any instantaneous parameter measured or calculated by the device into analogue signals by incorporating analogue output expansion modules.
- Track the status of components in the installation by using the status of the inputs to the expansion module.
- SPECIFICATIONS
- AC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 3 … 8 VA
- Frequency
- 50 … 60 Hz
- Nominal voltage
- 80 … 264 V ~
- DC POWER SUPPLY
- Installation category
- CAT III 300 V
- Consumption
- 2 … 3 W
- Nominal voltage
- 100 … 300 Vdc
- MECHANICAL CHARACTERISTICS
- Size (mm) width x height x depth
- 5 x 118 x 70 (mm)
- Screw type
- Flat, M2.5
- Envelope
- Self-extinguishing V0 plastic
- Torque setting
- ≤ 0.4 Nm
- Cable gauge at power supply terminals
- 5 mm2
- Cable gauge at input and output terminals
- 2,5 mm 2
- Fastening
- DIN rail (IEC 60715)
- Weight (kg)
- 0,228
- ENVIRONMENTAL CHARACTERISTICS
- Protection class
- IP30, Front: IP40
- Relative humidity (without condensation)
- 5 … 95%
- Storage temperature
- -20 … +70 ºC
- Working temperature
- -10 … +50 ºC
- STANDARDS
- Certifications
- UL 61010-1
- Electrical safety, Maximum height (m)
- 2000
- Standards
- UNE-EN 61010-1, UNE-EN 61010-2-30, UNE-EN 61326-1
- CURRENT MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Nominal current (In)
- …/5 A, …/1 A, …/0.250A (transformers type MC)
- Phase current measuring range
- (In: …/5 A): 0.01 … 10 A(In: …/1 A): 0.01 … 2 A(In: …/0.250 A): 0.01 … 0.5 A
- Maximum input current consumption
- 9 VA
- Maximum pulse current
- 100 A (< 1s)
- Minimum current measurement
- 01 A
- VOLTAGE MEASUREMENT CIRCUIT
- Installation category
- CAT III 300 V
- Sampling frequency
- 47 … 63 Hz
- Input impedance
- 1 MΩ
- Voltage measuring range
- 20 … 300 V ~
- Nominal voltage
- 300 V Ph-N / 520 V Ph-Ph
- Minimum measurement voltage (Vstart)
- 10 V ac
- COMMUNICATIONS
- Fieldbus
- RS-485
- Stop bits (ModBus)
- 1-2
- Parity
- non-pair-impar (Modbus)
- Protocol
- Modbus/RTU
- Speed
- 9600-19200-34800-57600-76800-115200 bps
- USER INTERFACE
- LED
- 2 LED
- Keyboard
- 3 keys
- Display type
- TFT RGB 1.77″ 160×128 pixel
- DIGITAL TRANSISTOR OUTPUTS
- Pulse width
- 1 ms
- Quantity
- 2
- Type
- Optocoupler NO
- Maximum frequency
- 500 Hz
- Maximum current
- 120 mA
- Maximum voltage
- 48 Vcc
- MEASUREMENT ACCURACY
- Frequency measurement
- …/5A (Class 0.1 % for three-phase and phase values), Class 0.1 % ( …/1A, …/0.250A)
- Phase current measurement
- …/5A, …/1A (class 0.2 % for three-phase and phase values), … / 0.250 A (class 1 % for I ≥ 20 % In, for three-phase and phase values)
- Reactive energy measurement (kvarh)
- Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
- Reactive power measurement (kvar)
- …/5A (class 1 % for three-phase and phase values), …/1A (class 1 %), …/0.250A (class 2 %)
- Apparent power measurement (kVA)
- …/5A (Class 0.5 % for three-phase and phase values), …/1A (Class 1 % for I ≥ 5 % In), … / 0.250 A (Class 1 % for I ≥ 20 % In)
- Active energy measurement (kWh)
- Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
- Power factor measurement
- …/5A (class 0.5 % for three-phase and phase values), class 0.5 % ( …/1A, … /0.250A)
- Phase voltage measurement
- …/5A, …/1A, …/0.250A (Class 0.2 % for three-phase and phase values)
Reviews