Line-CVM-D32

Compare
Category:

Description

Line-CVM-D32, Power analyzer

Code: M58100.

  • Protocol: Modbus/RTU
  • Communications: RS-485 | Bus-Line
  • Transistor output: 2
  • Measuring current Channels: 3
  • Harmonics: 40
  • Input current: …/5 A | …/1 A | …/250 mA
  • Mounting: DIN rail

 

INFORMATION

DESCRIPTION

The Line-CVM-D32 is a power analyser that measures, calculates and displays the main electrical parameters in single-phase networks, in systems with two phases without ground, with ARON connections or balanced or unbalanced three-phase systems. The measurement is a true RMS that relies on 3 AC voltage inputs and 3 current inputs. The device is modular and scalar thanks to expansion modules with different functionalities. The current is measured indirectly using /5A, /1A or /250mA transformers The voltage is measured directly in networks of up to 300V ~ P-N or through voltage transformers. Supply quality events counter (Overvoltages, gaps and interruptions)

APPLICATIONS

  • Measurement of electrical parameters in switchboards and low- and medium-voltage connections where space constraints require installing a space-saving analyser in the DIN rail.
  • Measurement of instantaneous, maximum and minimum values of electrical parameters.
  • Logging of consumed or generated Active or Reactive Energy.
  • Pricing of electricity in up to 4 tariffs (via communications or expansion module inputs)
  • Generation of impulses through outputs to a transistor, fully and independently configurable based on any incremental parameter of active or reactive energy, either per total counter or per tariff.
  • The installation can be controlled by way of programmable timer on delay, timer off delay and interlock alarms.
  • Ability to expand the analyser’s features by using expansion modules with transistor, relay or analogue inputs/outputs.
  • Convert any instantaneous parameter measured or calculated by the device into analogue signals by incorporating analogue output expansion modules.
  • Track the status of components in the installation by using the status of the inputs to the expansion module.
  • SPECIFICATIONS
  • AC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 3 … 8 VA
  • Frequency
  • 50 … 60 Hz
  • Nominal voltage
  • 80 … 264 V ~
  • DC POWER SUPPLY
  • Installation category
  • CAT III 300 V
  • Consumption
  • 2 … 3 W
  • Nominal voltage
  • 100 … 300 Vdc
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 5 x 118 x 70 (mm)
  • Screw type
  • Flat, M2.5
  • Envelope
  • Self-extinguishing V0 plastic
  • Torque setting
  • ≤ 0.4 Nm
  • Cable gauge at power supply terminals
  • 5 mm2
  • Cable gauge at input and output terminals
  • 2,5 mm 2
  • Fastening
  • DIN rail (IEC 60715)
  • Weight (kg)
  • 0,228
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • IP30, Front: IP40
  • Relative humidity (without condensation)
  • 5 … 95%
  • Storage temperature
  • -20 … +70 ºC
  • Working temperature
  • -10 … +50 ºC
  • STANDARDS
  • Certifications
  • UL 61010-1
  • Electrical safety, Maximum height (m)
  • 2000
  • Standards
  • UNE-EN 61010-1, UNE-EN 61010-2-30, UNE-EN 61326-1
  • CURRENT MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Nominal current (In)
  • …/5 A, …/1 A, …/0.250A (transformers type MC)
  • Phase current measuring range
  • (In: …/5 A): 0.01 … 10 A(In: …/1 A): 0.01 … 2 A(In: …/0.250 A): 0.01 … 0.5 A
  • Maximum input current consumption
  • 9 VA
  • Maximum pulse current
  • 100 A (< 1s)
  • Minimum current measurement
  • 01 A
  • VOLTAGE MEASUREMENT CIRCUIT
  • Installation category
  • CAT III 300 V
  • Sampling frequency
  • 47 … 63 Hz
  • Input impedance
  • 1 MΩ
  • Voltage measuring range
  • 20 … 300 V ~
  • Nominal voltage
  • 300 V Ph-N / 520 V Ph-Ph
  • Minimum measurement voltage (Vstart)
  • 10 V ac
  • COMMUNICATIONS
  • Fieldbus
  • RS-485
  • Stop bits (ModBus)
  • 1-2
  • Parity
  • non-pair-impar (Modbus)
  • Protocol
  • Modbus/RTU
  • Speed
  • 9600-19200-34800-57600-76800-115200 bps
  • USER INTERFACE
  • LED
  • 2 LED
  • Keyboard
  • 3 keys
  • Display type
  • TFT RGB 1.77″ 160×128 pixel
  • DIGITAL TRANSISTOR OUTPUTS
  • Pulse width
  • 1 ms
  • Quantity
  • 2
  • Type
  • Optocoupler NO
  • Maximum frequency
  • 500 Hz
  • Maximum current
  • 120 mA
  • Maximum voltage
  • 48 Vcc
  • MEASUREMENT ACCURACY
  • Frequency measurement
  • …/5A (Class 0.1 % for three-phase and phase values), Class 0.1 % ( …/1A, …/0.250A)
  • Phase current measurement
  • …/5A, …/1A (class 0.2 % for three-phase and phase values), … / 0.250 A (class 1 % for I ≥ 20 % In, for three-phase and phase values)
  • Reactive energy measurement (kvarh)
  • Class 1 (…/5A), Class 2 (…/1A, …/0.250A)
  • Reactive power measurement (kvar)
  • …/5A (class 1 % for three-phase and phase values), …/1A (class 1 %), …/0.250A (class 2 %)
  • Apparent power measurement (kVA)
  • …/5A (Class 0.5 % for three-phase and phase values), …/1A (Class 1 % for I ≥ 5 % In), … / 0.250 A (Class 1 % for I ≥ 20 % In)
  • Active energy measurement (kWh)
  • Class 0.5S (…/5A), Class 1 (…/1A), Class 1 (…/0.250A)
  • Power factor measurement
  • …/5A (class 0.5 % for three-phase and phase values), class 0.5 % ( …/1A, … /0.250A)
  • Phase voltage measurement
  • …/5A, …/1A, …/0.250A (Class 0.2 % for three-phase and phase values)

 

Reviews

There are no reviews yet.

Be the first to review “Line-CVM-D32”