RBZ-50-400

Compare
Category:

Description

RBZ-50-400, Reactors III for detuned filters

Code: P73145.

  • L(mH): 0,76
  • For capacitor: 2 x CLZ-FP-46/30
  • In (A): 72
  • Frequency (Hz): 50
  • kvar (400 V): 50
  • Losses: 189
  • Un (V): 400

 

INFORMATION

DESCRIPTION

CIRCUTOR has a complete range of detuned reactors, p = 7%, with a resonance frequency of 189 Hz for 50 Hz networks (or, on demand, 227 Hz for 60 Hz networks). This is the most frequent tuning value to avoid any resonance with the 5th harmonic and over. The set of capacitors-reactors absorbs part of the current of the 5th harmonic and acts as a detuned filter for higher frequencies. In some installations, anyway, other value of p(%) can be required, for example, 8,7 % (170 Hz), 14 % (134 Hz)…. CIRCUTOR can manufacture reactors adapted to any power, p (%), frequency, voltage (Un ≤ 1000 VAC).

Reactors for low power rating, RZ range, are built with low losses magnetic sheets and coiled with aluminum wires. A terminal block for the connection of the reactor is fitted. Higher powers are covered by RBH range. These reactors are based on a magnetic sheet core with multiple air gaps, which provides them with excellent characteristics and low loss ratios.

Both RZ and RBZ reactors are subjected to a varnish vacuum impregnation, based on polyester resin, to increase the insulation, providing a greater mechanical resistance and reducing the level of noise.

 

APPLICATIONS

RZ and RBZ detuned reactors have been specially designed for their use in installations with capacitor banks with considerably high harmonic distortion rates. The reactors must be connected in series to the proper power capacitor for the satisfactory protection of the own capacitors and to avoid the resonance effects in the installation.

SPECIFICATIONS

AC POWER SUPPLY

Frequency

50 Hz

ELECTRICAL CHARACTERISTIC

Overvoltage factor (p %)

7 % (189 Hz)

MECHANICAL CHARACTERISTICS

Size (mm) width x height x depth

255 x 220 x 145 (mm)

Envelope

Conductor type: Aluminium strip / copper cable

Weight (kg)

25

ENVIRONMENTAL CHARACTERISTICS

Thermal Class

class F (+155 ºC) On request: class H (+180 ºC)

Protection class

IP 00

Ambient temperature

-10 … +45 ºC

ELECTRICAL CHARACTERISTICS

Linearity (5% L)

1,75 x In

Maximum transient current

2 In (1 min)

Voltage

400 V,on request: up to 1000 V

Tolerance L

± 5 %

L value (mH)

0.76

Insulation voltage, circuit

3 kV

CURRENT MEASUREMENT CIRCUIT

Permanent overload

1,17 x In

STANDARDS

Standards

UNE-EN 60289, IEC 60076

 