Description
RGU-10C, Residual current relay
Code: P11944.
- Protocol: Modbus/RTU
- Módules: 3
- Pre-alarm relay: Yes
- Communications: RS-485
- Nº relays: 1
- IΔn (A): 0,03 … 3 A | 0,03 …30 A
- Power supply (Vac): 230 Vac
- Delay: 0,02 … 10 s, INS, SEL
- Mounting: DIN rail
INFORMATION
DESCRIPTION
Electronic residual current protection relay of the WG series, connected to the external transformers of the WG / WGC series. Superimmunized type relay with high frequency currents filtering and high immunity. True RMS measurement (TRMS).
- Data shown on the display
- Features two independent programmable outputs (main and prealarm)
- External input for remote-control functions (230 Vac)
APPLICATIONS
The RGU-10 relays associated with WG transformers offer smart residual current protection. Their design features guarantee maximum security and electrical service continuity, avoiding unwanted tripping.
Viewing the instantaneous leakage value on the display, together with the prealarm indicators, makes it possible to obtain information on the status of lines to be protected, and to perform adequate preventive maintenance.
In addition, version RGU-10 C features RS-485 communications and, with the PowerStudio software, offers centralised supervision in real time, as well as keeping a log of historical data for future analysis.
SPECIFICATIONS
AC POWER SUPPLY
Consumption
6 VA
Frequency
50/60 Hz
Nominal voltage
110 – 230 V~ (± 20 %)
MECHANICAL CHARACTERISTICS
Size (mm) width x height x depth
52.5 x 85 x 67.9 (mm)
Cable length to be stripped (mm)
7
Torque setting
0.5-0.6 Nm
Cable gauge at power supply terminals
0.5 … 2 mm2
Fastening
DIN rail
Weight (kg)
0,255
ENVIRONMENTAL CHARACTERISTICS
Protection class
IP 20 (terminals), IP 41 (front)
Relative humidity (without condensation)
5 … 95 %
Ambient temperature
-40 … +85 ºC
Working temperature
-10 … +50 ºC
COMMUNICATIONS
Stop bits (ModBus)
8
Parity
Non-pair-impar
Protocol
Modbus/RTU
Speed
9600 … 115200 Bd
Peripheral number
1 … 99
EXTERNAL RESET INPUT FOR TRIPPING
Type
Optocoupled
Maximum power
0,7 W
Maximum voltage
230 Vca ± 20%
STANDARDS
Electrical safety, Maximum height (m)
2000
Electrical safety, Installation category
CAT III 300V ca, IEC 61010
Standards
IEC 61008.1, IEC62020, IEC60947-2 Anexo M, IEC 60755
ELECTRICAL SAFETY
Insulation
Double-insulated electric shock protection class II (IEC 61010-1)
DIGITAL RELAY OUTPUTS
Nominal load in AC
2500 VA
Nominal current
6 A ~
Nominal voltage
250 V ~
Maximum current
10 A ~
Mechanical life
10 x 106
DIFFERENTIAL PROTECTION
Type
Type A ultra-immunised
Sensitivity (I∆n), A
0,03 … 3 / 5-10-30 (Setup)
Transformer
External, WG/WGC series
PROTECTION
Circuit breaker type
Contactor or Circuit Breaker + trigger coil
Reviews
There are no reviews yet.