Line-M-4IO-A

Compare
Category:

Description

Line-M-4IO-A, Expansion modules

Code: M58E03.

  • Protocol: Modbus/RTU
  • Analogue Inputs: 4 (0/4 … 20 mA)
  • Communications: Bus-Line
  • Analog output: 4 (0/4 … 20 mA) |4 (0/2 … 10 Vdc)
  • Mounting: DIN rail

 

INFORMATION

DESCRIPTION

Module with 4 analogue inputs and outputs Can be used to integrate 0-4…20mA analogue signals from control devices and sensors. The module has outputs to replicate the signals recorded through its inputs or to convert the parameters measured by the Line system devices in analogue form, 0/4…20mA or 0/2…10V, for management through external devices.

The expansion modules of the Line range provide a simple way to extend the features of any version of line-EDS-Cloud, line-EDS-PS, or of the line-CVM-D32 network analyser.

The modules are connected laterally and are detected automatically when the lateral connection is made, which greatly simplifies the installation and configuration of the modules.

APPLICATIONS

  • Expansion of inputs/outputs from line-CVM-D32 or line-EDS network analysers.
  • Convert any instantaneous parameter measured or calculated by the device into analogue signals by incorporating analogue output expansion modules.
  • Track the status of components in the installation by using the analogue inputs to the module.
  • SPECIFICATIONS
  • DC POWER SUPPLY
  • Consumption
  • 3 W
  • MECHANICAL CHARACTERISTICS
  • Size (mm) width x height x depth
  • 5 x 108 x 70 (mm)
  • Screw type
  • Flat, M2.5
  • Envelope
  • Self-extinguishing V0 plastic
  • Torque setting
  • ≤ 0.4 Nm
  • Cable gauge at power supply terminals
  • 5 mm2
  • Cable gauge at input and output terminals
  • 2,5 mm 2
  • Fastening
  • DIN rail (IEC 60715)
  • Weight (kg)
  • 0,134
  • ENVIRONMENTAL CHARACTERISTICS
  • Protection class
  • IP30, Front: IP40
  • Relative humidity (without condensation)
  • 5 … 95%
  • Storage temperature
  • -20 … +70 ºC
  • Working temperature
  • -10 … +50 ºC
  • VOLTAGE MEASUREMENT CIRCUIT
  • Input impedance
  • 150 Ω
  • STANDARDS
  • Electrical safety, Maximum height (m)
  • 2000
  • Electrical safety, Installation category
  • CAT III 300 V
  • Standards
  • UNE-EN 61010-1, UNE-EN 61000-6-2, UNE-EN 61000-6-4
  • USER INTERFACE
  • LED
  • 9 LED
  • ANALOGUE INPUTS
  • Quantity
  • 4
  • Input impedance
  • 150 Ω
  • Nominal input range
  • 0 … 20 mA / 4 … 20 mA (Programmable)
  • Measurement type
  • current
  • Maximum allowable neutral current
  • 22 mA dc
  • Accuracy
  • < 1 %
  • ANALOGUE OUTPUTS
  • Quantity
  • 4
  • Linearity
  • < 1 %
  • Current mode, nominal range
  • 0 … 20 mA / 4 … 20 mA
  • Current mode: maximum load resistance
  • 300 Ω
  • Voltage mode, minimum load resistance
  • 5 kΩ
  • Voltage mode: nominal output range
  • 0 … 10 V
  • DAC resolution
  • 4096 points
  • Maximum internal voltage
  • 12 V
  • Accuracy
  • 1 % (0 … 20 mA / 0 … 10 V)

 

Reviews

There are no reviews yet.

Be the first to review “Line-M-4IO-A”

Your email address will not be published. Required fields are marked *